Operator’s Manual017-201-B0 Rev. E5 Effective: January 2006Alpha TechnologiesNovus FXM 500 / 1100 / 1500 / 2000Uninterruptible Power Supply

Strona 2 - Alpha Technologies

6Introduction1.3 The FXM Front Panel (Continued)1.3.1 FXM 1100, 1500, 20001 Battery Circuit BreakerThis circuit breaker provides overcurrent protectio

Strona 3

7Introduction1.3 The FXM Front Panel (Continued)5 LCD Control PanelThis panel and the cancel, scroll and select buttons below it let you monitor and c

Strona 4 - Table of Contents

8IntroductionFigure 1.3.3A shows the dry contact’s layout while Figure 1.3.3B shows the +48VDC or +24VDC terminal block layout. Figure 1.3.4 shows one

Strona 5

9Introduction1.3 The FXM Front Panel (Continued)10 User InputThese optically isolated inputs let you attach an external switch panel for remote contro

Strona 6

10Introduction12 Input Circuit BreakerThis circuit breaker is an on/off switch for line power into the UPS and provides input protection. It must be o

Strona 7

11InstallationThis Section Tells You How to Install and Wire the Novus FXM UPSSite Preparation Instructions (Section 2.1)How to Mount the UPS (Section

Strona 8

12Installation2.1 Site Preparation Checklist GroundingThe UPS MUST be correctly grounded for proper operation.Older facilities may have inadequate ele

Strona 9 - Figure 1.3.2

13Installation2.2 Mounting the UPSThe UPS can be placed on a shelf with no other parts needed. Any version of the FXM can be rack or wall mounted or s

Strona 10 - Introduction

14Installation2.3 Wiring the External BatteriesDANGER: Before starting, make sure you have read the instructions on battery safety in Section 1.1 of t

Strona 11 - Continued on the Next Page

15Installation2.3 Wiring the External Batteries (Continued)Procedure1. Number the batteries from 1 to 4 with labels or tape as shown in Figure 2.3.1.

Strona 12 - Microprocessor

PowerAlpha Technologies®

Strona 13 - UPS Contact C7

16Installation2.4 Wiring the UPSDANGER: Before starting, make sure line power is turned off and that the UPS’s battery and input circuit breakers are

Strona 14 - FXM 500 Front Panel

17OperationThis Section Tells You How To Operate the Novus FXM How to use the LCD Control Panel and its Buttons to Operate the UPS (Section 3.1)How to

Strona 15 - Installation

18Operation3.1 Operating the Control PanelThe LCD control panel provides “at a glance” monitoring. This panel, when used along with the CANCEL, SCROLL

Strona 16 - Grounding

19Operation3.1 Operating the Control Panel (Continued)Pressing the CANCEL, SCROLL and SELECT buttons allow you to navigate through the menus and subme

Strona 17 - UPS Mounting

20OperationIf the UPS constantly switches between Inverter and Line modes due to a noisy line, the UPS’s input parameters should be broadened from nor

Strona 18 - Continued on the next page

21Operation3. Turn off the input circuit breaker.The LCD shows INVERTER, the status LED starts ashing to show the UPS is running on backup battery p

Strona 19 - Battery #4

22OperationWhile the batteries are being replaced, the UPS cannot provide backup battery power. This procedure should NOT be done when critical loads

Strona 20

23Operation3.4 Operating the UPSThe Control Submenu (Figure 3.4.1) lets you operate the UPS or program it to suit your operating conditions. You can a

Strona 21 - Operation

24OperationControl SubmenuLCD Shows Meaning DescriptionBATT TEST Battery Test This is the UPS’s self test. When it is turned on, this forces the UPS t

Strona 22 - 120/60/N

25Operation3.5 Making MeasurementsThe System Status Submenu (Figure 3.5.1) lets you make measurements of various UPS inputs, outputs and other values.

Strona 23

Uninterruptible Power SuppliesFrom Alpha Technologies017-201-B0 Rev. E5 1 / 06Operator’s ManualNovus FXM 500 / 1100 / 1500 / 2000

Strona 24 - Continued On the Next Page

26OperationSystem Status SubmenuLCD Shows Meaning DescriptionDATE DateThe date and time (24 hour clock).TIME TimeINV COUNT Inverter Count The number o

Strona 25

27OperationWhen the front panel alarm LED is on or ashing, the UPS is malfunctioning. The Alarm and Fault Submenus describe the malfunction. You can

Strona 26 - Control Panel Tutorial

28Operation3.6 Troubleshooting (Continued)Fault SubmenuLCD Shows DescriptionOVERLOAD FAULT The load draws more power than the UPS can provide. This ca

Strona 27 - MENUS

29Operation3.7 Last Event LogThe Event Submenu displays the last event the UPS went through. To use the 100-event log, see Section 4.5, “Accessing the

Strona 28 - Control Submenu

30CommunicationThis Section Tells You How To Operate the Novus FXM With RS-232 Computer Commands How to Wire the RS-232 Port (Section 4.1)How to Use t

Strona 29 - System Status Submenu

31Communication4.1 Wiring the RS-232 PortThe UPS’s front panel has a DB-9 female connector. When connected to a PC with Window’s HyperTerminal or othe

Strona 30

32Communication4.2 Using the Main MenuThe UPS’s main menu screen runs on a command line system. This program does not recognize the backspace or delet

Strona 31 - OVERLOAD

33Communication4.2 Using the Main Menu (Continued)4.2.2 RS-232 Menu TreeSubmenus 1, 2 and 4 provide read-only screens for monitoring the UPS. To contr

Strona 32 - LCD Shows Description

34Communication4.2 Using the Main Menu (Continued)Line StatusNormal The line is within specications. The UPS is operating in Line mode.Boost Line vol

Strona 33

35Communication4.2 Using the Main Menu (Continued)4.2.5 Fault and Alarm DisplaysThese display any malfunctions the UPS has (Also see Section 3.6).Faul

Strona 34 - Communication

Novus FXM 500/1100/1500/2000 Operator’s ManualSave This Manual: It contains important installation and operating instructions. Keep it in a safe place

Strona 35 - Parameters

36Communication4.3 Operating the UPSThe Maintenance submenu (Figure 4.3.1) lets you control the UPS and change selected items to meet your operational

Strona 36

37Communication4.4 Programming the Dry Contacts and the ClockThe UPS’s front panel contacts (Section 1.3.1) can be programmed to meet your specicatio

Strona 37 - (Figure 4.2.1)

38Communication4.4.2 Setting the Timer Contact The front panel’s timer contact (Section 1.3.1; C4 and Section 4.4.1) can be programmed to suit your co

Strona 38

39CommunicationUp to 100 events are stored in the UPS’s log. If more than 100 events occur, the oldest is over written.Procedure1. To see the log, ty

Strona 39

40Communication3. To clear the log, type eventclr and press ENTER. It takes the UPS 30 seconds to clear the log. Do not enter any other commands duri

Strona 40 - Maintenance Submenu

41Communication4.6 Novus FXM Graphical User Interface4.6.1 IntroductionThe Novus FXM RS–232 Graphical User Interface (GUI) works like a Web or Windows

Strona 41

42CommunicationProcedure1. Install the FXM Monitor software onto your computer. Restart the computer.If you install the FXM Monitor on a version of W

Strona 42

43Communication4.6 Novus FXM Graphical User Interface (Continued)UPS SPECIFICATIONSThis read-only screen shows the UPS’s factory specications.UPS MON

Strona 43

44CommunicationUPGRADE FILESThis screen lets you update UPS’s internal software (See Section 5.1, “Updating the Software”). You must have already down

Strona 44

45MaintenanceThis Section Tells You How To Maintain the Novus FXM How to Replace the Software (Section 5.1)•5

Strona 45 - Figure 4.6.1

1IntroductionThis Section Introduces the Novus FXM Uninterruptible Power Supply (UPS)Safety Instructions (Section 1.1)Unpacking and Inspection Instruc

Strona 46

46Maintenance5.1 Updating the SoftwareThe UPS’s rmware can be reinstalled or updated to the latest version with this procedure.Tools and Materials Re

Strona 47

47SpecicationsMechanical SpecicationsFXM 1100/1500/2000 Dimensions, in (mm) H x W x D5.2 x 15.5 x 8.75(133 x 394 x 222)FXM 1100/1500/2000 Weight, lb

Strona 48

48SpecicationsBoost/Buck/Line Transfer ThresholdsSubject to change without noticeParameter 120VAC Units 230VAC UnitsHigh Line TransferHigh Line Retra

Strona 49 - Maintenance

49Index100 Event log, RS-232 ...39-4024VDC, FXM 500 ...54

Strona 50 - Alpha FXM ISP

50Indexmaintenance submenu ...33, 36main menu, use of ...

Strona 51 - Specications

51IndexINV BYPASS ...24INV RECORD ...

Strona 52 - Regulatory

52Index...20System status menu ...

Strona 53

53IndexVOLTAGE ...24VOUT ...

Strona 54

54WarrantyLIMITED 24-MONTH WARRANTYAC PRODUCTSAlpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanshi

Strona 55

Emergency Shutdown ProcedureThe Novus FXM has more than one live circuit. In an emergency, line power may be disconnected at the input, but there can

Strona 56

2Introduction1.1.1 UPS Safety ChecklistThis Uninterruptible Power Supply (UPS) is to be installed by people trained in the safe use of high-energy pow

Strona 57

PowerAlpha Technologies®Due to continuing product improvements, Alpha reserves the right to change specications without notice. Copyright © 2006 Alph

Strona 58 - AC PRODUCTS

3Introduction1.1.2 Battery Safety ChecklistBattery Emergency ProceduresIf electrolyte splashes on your skin, immediately wash the affected area with w

Strona 59 - Emergency Shutdown Procedure

4IntroductionIf items are missing or damaged, contact Alpha Technologies and the shipping company at once. Most shippers have a short claim period.Car

Strona 60

5Introduction1.3 The FXM Front PanelThe FXM 500 and the FXM 1100/1500/2000 series look different, but all of the front panel connectors and circuit br