Alpha Technologieswww.alpha.comOperator’s Manual017-201-B0 Rev 05/07Novus FXM 650 / 1100 /2000Uninterruptible Power Supply
1 Battery BreakerThis circuit breaker provides overcurrent protection and is an on/off switch for battery power. It must be on for proper UPS operatio
5 LCD Control PanelThis panel and the cancel, scroll and select buttons below it let you monitor and control the UPS. More information is given in Sec
9 Contacts C1 to C6Contacts C1 to C5 allow you to connect the UPS to an external monitoring panel or to trafc control equipment.The factory default s
10 Contacts C7 and C8These optically isolated inputs let you attach an external switch panel for remote control of the UPS or have the UPS control Alp
12 Input Circuit BreakerThis circuit breaker is an on/off switch for line power into the UPS and provides input protection. It must be on for proper U
11InstallationThis Section Tells You How to Install and Wire the Novus FXM UPSSite Preparation Checklist (Section 2.1)• Mounting the UPS (Section 2.2)
2.1 Site Preparation Checklist F Grounding The UPS MUST be correctly grounded for proper operation. Older facilities may have inadequate electrical g
2.2 Mounting the UPSThe UPS can be placed on a shelf with no other parts needed. Any version of the FXM can be rack or wall mounted or secured to a sh
2.3 Wiring the External Batteries DANGER: Before starting, make sure you have read the instructions on battery safety in Section 1.1 of this manual.To
Procedure1. For FXM 1100/2000 and FXM 650-48 (48 V battery string), number the batteries from 1 to 4 with labels or tape as shown in Figure 2.3.1a. F
PowerAlpha Technologies®
DANGER: Before starting, make sure line power is turned off and that the UPS’s battery and input circuit breakers are turned off. If stranded wires a
DANGER: Before proceeding, verify the line wire is attached to the line terminal block, the ground wire is attached to the ground terminal block and
18OperationThis Section Tells You How to Operate the Novus FXMOperating the Control Panel (Section 3.1)• Turning the UPS On and Off (Section 3.2) • Re
3.1 Operating the Control PanelThe LCD control panel provides “at a glance” monitoring. This panel, when used along with the CANCEL, SCROLL and SELECT
Pressing the CANCEL, SCROLL and SELECT buttons let you to navigate through the menus and submenus to control, monitor and troubleshoot the UPS as show
3.2 Turning the UPS On and OffIf the UPS constantly switches between Inverter and Line modes due to a noisy line, the UPS’s input parameters should be
3. Turn off the input circuit breaker.The LCD shows INVERTER, the status LED starts ashing to show the UPS is running on backup battery power. Make
3.3 Replacing the BatteriesDuring battery replacement the UPS cannot provide backup battery power. This procedure should NOT be done when critical loa
The control menu (Figure 3.4.1) lets you operate the UPS or program it to suit your operating conditions. You can also use the Novus User Software to
Control Menu (Continued)BATT TEST Battery Test This is the UPS’s self test. When it is turned on, the UPS is forced to verify its proper operation by
Uninterruptible Power SuppliesAlpha Technologies www.alpha.com017-201-B0 Rev. 02 / 07Operator’s ManualNovus FXM 650 / 1100 / 2000FXM 650FXM 1100/2000
3.5 Making MeasurementsThe system status menu (Figure 3.5.1) lets you make measurements of various UPS inputs, outputs, temperatures and other values.
System Status MenuDATE Date The date and time (24 hour clock).TIME TimeINV COUNT Inverter Count The number of times the UPS was in inverter mode.INV T
3.6 Troubleshooting the UPSWhen the front panel alarm LED is on or ashing, the UPS has a malfunction. The alarm and fault submenus (Figure 3.6.1) des
Fault SubmenuLCD Shows DescriptionOverload Fault The load draws more power than the UPS can provide. This can lead to an automatic UPS shutdown. Remov
3.7 Viewing the 25-Event LogThe event menu displays on the LCD the last 25 events the UPS went through and the malfunction that triggered it. If more
31CommunicationThis Section Tells You How To Operate the Novus FXM With RS-232 Computer Commands How to Wire the RS-232 Port (Section 4.1)• How to Use
4.1 Wiring the RS-232 PortThe UPS’s front panel has a DB-9 female connector. When connected to a PC with Window’s HyperTerminal or other terminal emul
4.2 Using the Main MenuThe UPS’s main menu screen runs on a command line system (Figure 4.2.1). This program does not recognize the backspace or delet
4.2.2 RS-232 Menu TreeSubmenus #1, 2 and 4 are read-only screens for monitoring the UPS. To control the UPS, use submenu #3, the Maintenance submenu.1
4.2.3 Line StatusLine status tells you the line’s condition (Also see Figure 3.1.2). For an updated value, press ENTER.4.2.4 Output StatusOutput statu
Save This Manual: It contains important installation and operating instructions. Keep it in a safe place.Table of ContentsThe emergency shutdown proce
4.2.5 Fault and Alarm DisplaysThese display any malfunctions the UPS has (Also see Section 3.6).Line Status: NormalOutput Status: Line ModeFaults: Sho
4.3 Adjusting and Controlling the UPSThe Maintenance submenu (Figure 4.3.1) lets you control the UPS and change selected items to meet your operationa
4.4 Programming the Dry Contacts and the ClockThe UPS’s front panel contacts (Section 1.3.1, “FXM 1100/2000, Contacts C1 to C6”) can be programmed to
4.4.2 Setting the Timer Contact The front panel’s timer contact (Section 1.3.1, “FXM 1100/2000, Contacts C1 to C6” and Section 4.4.1) can be programme
Up to 100 events are stored in the UPS’s log. If more than 100 events occur, the oldest is over written.Procedure1. To see the log, type event (all l
4.6 Novus User Software4.6.1 IntroductionThe Novus User Software Graphical User Interface (GUI) provides Web or Windows© like computer communications
If you are downloading from Microsoft’s web site, you must have Internet Explorer installed on your computer. In addition to installing .NET, download
3. Set the communications parameters on your computer to:• COM Port: The COM port on your computer you have selected to use.• Baud Rate: 2400.4. T
UPS SPECIFICATIONThis read-only screen shows the UPS’s factory-set specications.UPS MONITORINGThese read-only screens show the UPS’s current input an
ALARMS & FAULTS This read-only screen shows you what malfunctions the UPS has (Also See Section 3.6, “Troubleshooting”). When the fault or alarm i
1IntroductionThis Section Introduces the Novus FXM Uninterruptible Power Supply (UPS)Safety Instructions (Section 1.1)• Unpacking and Inspection Instr
46MaintenanceThis Section Tells You How To Maintain the Novus FXM How to Replace the Software (Section 5.1)• 5
5.1 Updating the SoftwareThe UPS’s rmware can be reinstalled or updated to the latest version with this procedure.Tools and Materials Required• RS-2
6. Type (all lower case) oad(1 space);b and press ENTER. A pop-up appears asking you to locate the new rmware. Look for a “sx record” (*.sx). Selec
MechanicalSpecicationsDimensions, in (mm) H x W x D1100-2000: 5.22 x 15.5 x 8.75(133 x 394 x 222)650: 3.47 x 17 x 9(89 x 432 x 229)Weight, lb (kg)
Boost/Buck/Line Transfer ThresholdsSubject to change without noticeParameter 120VAC Units230VAC UnitsFXM 2000 (120VAC)High Line TransferHigh Line Retr
Note: Listings in BOLD ALL UPPER CASE are entries as displayed on the LCD panelSymbols100-Event Log ...4025-Event Log ...
Note: Listings in BOLD ALL UPPER CASE are entries as displayed on the LCD panelRRS-232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53IndexDoc# 017-201-B0 Rev 05/07This page is left blank intentionally.
54WarrantyLIMITED 24-MONTH WARRANTYAC PRODUCTSAlpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanshi
Emergency Shutdown ProcedureThe Novus FXM has more than one live circuit. In an emergency, line power may be disconnected at the input, but there can
1.1.1 UPS Safety ChecklistThis Uninterruptible Power Supply (UPS) must be installed in a restricted access location, and by trained personnel qualied
PowerAlpha Technologies®Due to continuing product improvements, Alpha reserves the right to change specications without notice. Copyright © 2007 Alph
1.1.2 Battery Safety Checklist Battery Emergency Procedures If electrolyte splashes on your skin, immediately wash the affected area with water. If e
If items are missing or damaged, contact Alpha Technologies and the shipping company at once. Most shippers have a short claim period.Carefully remove
1.3 The FXM Front PanelThe FXM UPS is available in 3 models – FXM 650, FXM 1100 and FXM 2000. The FXM 650 and the FXM 1100/2000 look different, but al