017-720-B2-001 03/97©1997 Alpha TechnologiesXM / XP 90V SERIESUninterruptible Power SuppliesXM 9015XM 1350TTechnical Manual
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATION5The XP Series Uninterruptible Power Supply consists of an XM Series power module, apole
017-720-B2-001 03/97©1997 Alpha Technologies62.2.2 Inverter (STANDBY) OperationWhen the incoming AC line voltage drops significantly, or a complete p
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATIONTo ensure operator safety:1. Power supplies should be installed only by qualified personne
017-720-B2-001 03/97©1997 Alpha TechnologiesPWE enclosures are designed to be mounted on wooden poles; however, special bracketsare available for con
017-720-B2-001 03/97©1997 Alpha Technologies9UPE and UPE/M enclosures are designed to bolt directly to a Pedestal Support orconcrete pad. Four 1/2&
017-720-B2-001 03/97©1997 Alpha TechnologiesUPE/M - Four 3/8" J-bolts should be centered with the pad 24" (side to side) and 14" (fron
017-720-B2-001 03/97©1997 Alpha Technologies112. INSTALLATION2.4 Ground-Mount EnclosuresCablePowerOutputUtilityPowerInputUPE UPE/MPedestal Support UP
017-720-B2-001 03/97©1997 Alpha Technologies12CAUTION: THE FOLLOWING SHOULD BE PERFORMED ONLY BY QUALIFIED SERVICEPERSONNEL AND IN COMPLIANCE WITH LO
017-720-B2-001 03/97©1997 Alpha Technologies13Procedure: (Refer to SPI drawing located at the back of the manual)1. Prepare the incoming coaxial cab
017-720-B2-001 03/97©1997 Alpha Technologies142. INSTALLATIONWHENEVER INSTALLING OR REPLACING BATTERIES, DO NOT ALLOW LIVE BAT-TERY WIRES TO CONTACT
017-720-B2-001 03/97©1997 Alpha Technologiesi
017-720-B2-001 03/97©1997 Alpha Technologies152. INSTALLATIONAttach the RTS BatteryTemperature Sensor to eitherside of the center battery usinghigh-
017-720-B2-001 03/97©1997 Alpha Technologies162. INSTALLATIONProcedure: (Refer to the Battery Wiring drawing located on the next page and at the back
017-720-B2-001 03/97©1997 Alpha Technologies172. INSTALLATIONRED +BLACK -NEGATIVEPOSITIVE123Optional In-Line FuseR.T.S.(Connects to Side of XM Module
017-720-B2-001 03/97©1997 Alpha Technologies182. INSTALLATIONXM Series power modules are placed in the upper-right compartment of CE, PWE, UPEand UPE
017-720-B2-001 03/97©1997 Alpha Technologies19The XM Series power module comes with a field-replaceable, main circuit moduleassembly containing the s
017-720-B2-001 03/97©1997 Alpha Technologies20The Main Circuit Module assembly comes equipped with circuitry to monitor incom-ing AC, charge the batt
017-720-B2-001 03/97©1997 Alpha Technologies212.10.2 Float and Equalize ChartIn a typical 3-battery system (36 VDC), if a particular battery manufact
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATION22The APM is a field-replaceable logic upgrade that allows the XM Series powermodule to se
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATION2.11 Automatic Performance Monitor (APM), cont'd.2.11.2 APM "Auto-Equalize"
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATIONThe optional, USM status monitoring upgrade plugs directly into the APM logic card.NOTE: T
017-720-B2-001 03/97©1997 Alpha TechnologiesTable of Contents1. SAFETY INSTRUCTIONS 12. INSTALLATION 42.1 Introduction 42.2 Theory of Operation 52.2.
017-720-B2-001 03/97©1997 Alpha Technologies252. INSTALLATIONXM Series Side Panel with USMNOTE: THE UNIT CAN CONTINUE TO OPERATE AS A NON-STANDBY POW
017-720-B2-001 03/97©1997 Alpha Technologies262. INSTALLATIONP1 (Tamper Switch)P2 (Tamper Switch)P3 (TRI-State Alarm)P5 (General Alarm)P4 (Output Ala
017-720-B2-001 03/97©1997 Alpha Technologies2. INSTALLATION27The input voltage of the XM9015 and XM1350T can be reconfigured from 240 VAC to120 VAC;
017-720-B2-001 03/97©1997 Alpha Technologies28CAUTION: Before applying power to the XM power module, verify that the 240 VACjumper on the backplane b
017-720-B2-001 03/97©1997 Alpha Technologies292. INSTALLATIONThe XM9015 and XM1350T can be reconfigured for 120 VAC operation by removingthe 240 VAC
017-720-B2-001 03/97©1997 Alpha Technologies30The XM9015 and XM1350T are equipped with multiple output voltage taps(90, 75 and 60 VAC). The units ar
017-720-B2-001 03/97©1997 Alpha Technologies316451 325XM Power Module Start-up and TestingAC Line Operation (LINE POWER)(Numerals refer to paragraphs
017-720-B2-001 03/97©1997 Alpha Technologies32Once connections have been made to the power module, it should be tested for AC LINEand STANDBY operati
017-720-B2-001 03/97©1997 Alpha Technologies33In order to fully understand the power supply functions, it is important to recognizethe modes of opera
017-720-B2-001 03/97©1997 Alpha Technologies343.2.2 Charger Status BlockThe CHARGER STATUS block indicates the battery charging modes: FLOAT,EQUALIZE
017-720-B2-001 03/97©1997 Alpha TechnologiesXM / XP 90V Series Uninterruptible Power SuppliesTable of Contents, continued4. MAINTENANCE 374.1 Data R
017-720-B2-001 03/97©1997 Alpha Technologies3.2.3 APM (Automatic Performance Monitor) Status BlockOn units equipped with an APM logic upgrade, the po
017-720-B2-001 03/97©1997 Alpha Technologies36XM90-S Service Power Supply (SPB95-538A)When a power module needs to be removed from service, an Alpha
017-720-B2-001 03/97©1997 Alpha Technologies37Preventive Maintenance using the optional DataLoggerXM Series Power ModuleBy automating data retrieval,
017-720-B2-001 03/97©1997 Alpha Technologies4. MAINTENANCE38Maintenance should be performed every three to six months. If the power module failsto p
017-720-B2-001 03/97©1997 Alpha Technologies394.2.3 Check Battery Voltage Under LoadThis is the most accurate method to determine the condition of th
017-720-B2-001 03/97©1997 Alpha Technologies404.2.7 Check Output CurrentCheck the module's output current. The front panel LED display is usefu
017-720-B2-001 03/97©1997 Alpha Technologies4. MAINTENANCE4.2.9 Main Circuit Module and Logic Board MaintenanceSERVICE AND CALIBRATION SHOULD ONLY BE
017-720-B2-001 03/97©1997 Alpha Technologies424.2 Preventive Maintenance, continued4.2.12 Repair InstructionsBefore returning a unit to Alpha Techno
017-720-B2-001 03/97©1997 Alpha Technologies43SYMPTOM PROBABLE CAUSE REMEDYNo output to cable; Utility power outage. Use voltmeter to verifyNo AC lin
017-720-B2-001 03/97©1997 Alpha Technologies44SYMPTOM PROBABLE CAUSE REMEDYLow output voltage whenunit is in STANDBY mode: Defective inverter transis
017-720-B2-001 03/97©1997 Alpha TechnologiesivCAUTIONRISK OF ELECTRICAL SHOCKCAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK,AND ENSURE THE SAFE OPER
017-720-B2-001 03/97©1997 Alpha Technologies454. MAINTENANCESYMPTOMIncorrect, or no float orequalize charge voltages:Battery breaker trips whenattemp
017-720-B2-001 03/97©1997 Alpha Technologies46Red "CHECK INVERTER" LEDand LRI lamp (if installed) flashing:4.2.14 Trouble Shooting Guide, c
017-720-B2-001 03/97©1997 Alpha Technologies475. SPECIFICATIONS5.1 Input/Output VoltagesOutputXM1350T-48 240 7.9 90 15 1350 48240 7.9 75 18 1350 4824
017-720-B2-001 03/97©1997 Alpha TechnologiesRegulationInput Voltage (VAC) +10 / -20%Input Frequency (Hz) +/- 3%Output Voltage (VAC) +/- 5%Output Freq
017-720-B2-001 03/97©1997 Alpha TechnologiesSpecifications @ 77°F (25°C) @ load.* Charger voltages should be user selected on the XM's Main Modu
017-720-B2-001 03/97©1997 Alpha Technologies506.1 Concrete Pad Layout6. ILLUSTRATIONSStud Placement for UPE/MConcrete Pad Mounting
017-720-B2-001 03/97©1997 Alpha Technologies516. ILLUSTRATIONSXM Series Power SupplyShown in PWE Enclosure6.2 PWE Enclosure
017-720-B2-001 03/97©1997 Alpha Technologies526.3 UPE-M Enclosure6. ILLUSTRATIONSXM Series in UPE-M Enclosure
017-720-B2-001 03/97©1997 Alpha Technologies536. ILLUSTRATIONS6.4 Block DiagramXM Series Power ModuleBlock Diagram
017-720-B2-001 03/97©1997 Alpha Technologies546.5 Side Panel6. ILLUSTRATIONSXM Series Side Panel
017-720-B2-001 03/97©1997 Alpha TechnologiesIMPORTANT TECHNICAL NOTECAUTION: When operating the XP Series Uninterruptible Power Supply, aminimum load
017-720-B2-001 03/97©1997 Alpha Technologies556.6 Output Wire Assembly6. ILLUSTRATIONSXM SeriesSingle to Dual OutputWire Assembly
017-720-B2-001 03/97©1997 Alpha Technologies566. ILLUSTRATIONSService Power Inserter (SPI)6.7 Service Power Inserter
017-720-B2-001 03/97©1997 Alpha Technologies586. ILLUSTRATIONS6.8 Dual SPI ArrangementAssembly, PWE 240V, Dual SPI
017-720-B2-001 03/97©1997 Alpha Technologies596. ILLUSTRATIONSInstallation Instructions,Battery heater6.9 Battery Heater
017-720-B2-001 03/97©1997 Alpha Technologies
017-720-B2-001 03/97©1997 Alpha Technologies
017-720-B2-001 03/97©1997 Alpha Technologies
017-720-B2-001 03/97©1997 Alpha Technologies
017-720-B2-001 03/97©1997 Alpha TechnologiesPrinted in the USA 017-720-B2-001 8/96USA & LATIN AMERICAAlpha Technologies3767 Alpha WayBelling