2 Installation
24
2.8 Connecting the External Alarm Port
An external alarm panel can be connected to the external alarm port (Figure 2.4). The port’s
contacts are rated at 30 VDC at 1 Amp.
An Emergency Power Off (EPO) switch is created by wiring a switch to Pins 7 and 8.
• Pushing the EPO switch automatically switches off the unit’s battery circuit breaker.
• The contacts must be shorted for at least 1.5 seconds with unit shutdown about 2 seconds
after the shorting starts.
• The switch must be a SPST, N.O. type and be electrically isolated (up to 1500 VAC
isolation is recommended). The connecting cable can be twisted or shielded wire not
more than 100 ft. (30 m) long.
CAUTION: The EPO switch does not disconnect the utility line. Switch off the circuit
breaker providing line power to the unit.
Figure 2.4
Wiring the External Alarm Port
87654321
EPO
Circuit
N.O. EPO Switch
N.C. Line
Present
N.C.
Battery OK
N.O. Line
Failure
N.O. Low
Battery Warning
Contact Rating:
30 VDC @ 1 Amp
UPS Internal
UPS External
18
RJ-45
Connector
(8-Pin Type)